Technical data
IN 48 Two-Wire Transducer
Resistance load:
200 Ω ... 2 KΩ
Analogue Output:
4 ... 20 mA
Voltage range:
12 ... 30 V DC
Admissible ripple voltage:
≤ mVss at 50 up to 100 Hz
max. load:
R = (U-12V) / 0.02 A
Sample with U = 24 V:
R = (24 V -12 V) / 0.02 A = max. 600 Ω
Dimensions:
70 x 45 x 28 mm (L x B x H)
Mounting:
Via DIN cap rail or two borehole (4 mm)
Alignment :
electrical zero and range adjustable
Test port:
4 ... 20 mA, max. load 10 Ω
witout interrupting the current loop
Basic circuit:
Other Products
IN 48 Two-Wire Transducer
Two-wire transducer from potentiometer input (0.2 - 2 KΩ) to current output (4-20 mA)